OML-IAR16 Auto Reclosing Earth Leakage Protector Source Lightning Protector
Product Description:
OMRDON automatic reclosing leakage protection is suitable for AC 50Hz/60Hz rated current up to 10A/16A/32A line, as the line and equipment over-voltage, low-voltage, over-current/short-circuit, leakage and other protection. It is suitable for electric equipment in various environments, such as communication base stations, repeater stations, video surveillance, safe city, cable TV, digital TV, network switches, optical transceivers, meteorological telemetry stations, seismic monitoring stations, photovoltaic power generation and other places.
The product adopts shielded shell package, built-in high quality high-speed over-voltage protection devices, the power line induction of lightning high-voltage pulse has a highly efficient protection and defense function.
Functional Features::
- pre-close detection
- overpressure protection
- overcurrent protection
- undervoltage protection
- leakage protection
- short circuit protection
- Automatic disconnection in case of power failure
- Zero line disconnection protection
- Intelligent Leakage Recognition
- Audible and visual fault alarms
- Remote monitoring (optional)
typical application
- Communications base stations
- Video Surveillance Distribution Cabinet
- meteorological telemetry station
- Seismic monitoring stations
- digital television
Technical Parameters
| Name | automatic reclosing | ||
| Model | OML-IAR10 | OML-IAR106 | OML-IAR63 |
| Rated load current | 10A | 16A | 63A |
| Nominal operating voltage Nominal operating voltage (Un) | 85-300VAC | ||
| Overcurrent action current | 1.15 In | ||
| Short circuit action current | 50A | ||
| Residual non-operating current | 15 mA | ||
| Residual operating current (adjustable) | 30 mA | ||
| Overvoltage action voltage (adjustable) | 260V±10V | ||
| Undervoltage action voltage (adjustable) | 150V±10V | ||
| Overcurrent disconnection action time Overcurrent disconnection action time | 2±0.5 s | ||
| Short circuit disconnection action time | ≤0.03 s | ||
| Leakage disconnection action time | ≤0.03 s | ||
| Overvoltage and undervoltage disconnection action time Overvoltage and undervoltage disconnection action time | ≤2 s | ||
| Allow reset of load impedance | 5 Ω | ||
| Lightning strike capability | 8/20us 20KA | ||
| Voltage detection before closing | there are | ||
| Reclosing time Reclosing time (adjustable) | 30S/0.5h/1h | ||
| Size | 95mm*93mm*65mm | ||
| Interface type | terminals | ||
| Work environment | Temperature range: -40℃~85℃; Humidity range: ≤95% RH; Atmospheric pressure: 70kPa; 106kPa; Storage temperature: -40℃~85℃. | ||
| Installation | in series connection (electricity) | ||
| Housing material | Flame Retardant Plastic (Rail Type) | ||
| Enclosure ratings | IP20 | ||
| Test basis | gb/t 18802.11.2020,iec61643-11-2011 | ||
Typical Performance Test Data

Simulated Lightning Impact Test

Product Dimension Drawing

Installation Precautions
1, the automatic reclosing power protector is installed on the wall or in the host box, avoid direct rain, sunshine.
2、Connect this product to the bottom of the circuit breaker (or gate switch), power supply to the input terminal, load to the output terminal.
3、If the red indicator light is on after 10 seconds of closing the power supply, it indicates that there is a corresponding fault in the line, turn off the switch for 10 seconds and then close it again. If still can't close the gate to send power, it indicates that the leakage current in the line exceeds the specified value, or there is overcurrent/short-circuit phenomenon in the line should be shut down all the loads, find out the reason immediately and remove the fault before sending power.
4, this automatic reclosing power protector can replace the existing leakage switch and circuit breaker in the installation of this automatic reclosing power protector, can not be used at the same time with the existing ordinary leakage switch, should be removed from the installed leakage protection switch.