Tel. +86-755-82591856     E-mail. info@omrdon.com

Shenzhen OMRDON TECHNOLOGY

---- specializes in lightning safety and protection.

OMS-RJ11/2S,OMS-LSA/10,电话防雷器,科隆防雷排,电话机/科隆配线架防雷保护 - 欧姆雷盾omrdon Technology

Signal line lightning protection/

OMS-RJ11/2S,OMS-LSA/10,Lightning protection for telephone,Lightning protection row of Cologne,Lightning protection for telephone/cologne distribution frame

name (of a thing)

Telephone lightning protector

model number

0MS-RJ11/2S

0MS-LSA/10

item number

800327

800326

SPD category

flammable

switching type

Nominal operating voltage Un

110VDC

110VDC

Maximum continuous operating voltage Uc

185VDC

230VDC

Nominal discharge current In

5kA 

5KA 

Maximum discharge current Imax

10kA 

10KA

protected circuit

2-wire (Pin2,3)

10 wires, set of 10 wires

Interface Type

RJ11 Crystal Head

LSA-PLUS

Housing Material

Flame retardant plastics

Flame retardant plastics

Overall dimensions

90×67×18mm

113×23×45mm

Installation

Series Connection Plug-In

KRONE Distribution Frame

  • 产品详情
  • Inquiry

OMS-RJ11/2S,0MS-LSA/10,110V,10KA telephone lightning protector, Cologne lightning protection row, telephone/cologne distribution frame lightning protection

Product Description:

    OMRDON OMS-RJ11/2S(4S),0MS-LSA/10 telephone lightning protector is designed according to IEC and international standards, mainly used for telecommunication data communication signal line and its equipment (such as: telephone, programmable telephone, fax machine, Cologne distribution frame) lightning, over-voltage protection, easy to install, without special maintenance.

     The product is encapsulated in a shielded case with a built-in high quality high-speed overvoltage protection device, which provides efficient protection and defense against lightning high-voltage pulses induced on the signal line.

Functional Features::

  • Large through-current capacity, low residual voltage and fast response time.
  • Internal two-stage series linkage protection, low residual voltage, long service life.
  • With triple protection function of over-current, over-voltage and clamping, fast response speed.
  • Low loss, superior signal transmission performance.
  • Provides wire-to-wire and wire-to-ground full protection modes.
  • Fast reaction time, less than 1ns.

typical application

  • telephones
  • fax
  • ADSL line
  • Krone Distribution Frame
  • Fire Alarm

Technical Parameters

name (of a thing)Telephone lightning protector
model number0MS-RJ11/2S0MS-RJ11/4S0MS-LSA/10
item number800327800328800326
SPD categoryflammableswitching type
Nominal operating voltage Un110VDC110VDC
Maximum continuous operating voltage Uc185VDC230VDC
Nominal discharge current In5kA 8/20μs5KA 8/20μs
Maximum discharge current Imax10kA 8/20μs10KA 8/20μs
Voltage protection level UpX-X≤320V≤350V
X-PE≤650V≤700V
Response time Ta≤1ns≤100ns
Insertion loss Ae≤0.3db
Transmission rate Vs10Mbps
temperature range-40°C ...+85°C
protected circuit2-wire (Pin2,3)4-Wire (Pin1,2,3,4)10 wires, set of 10 wires
Interface TypeRj11 Crystal HeadLSA-PLUS
Housing MaterialFlame retardant plasticsFlame retardant plastics
Overall dimensions90×67×18mm113×23×45mm
Ground Wire Diameter2.5mm2 or more2.5mm2 or more
InstallationSeries Connection Plug-InPlugs directly into KRONE wiring racks.

Simulated Lightning Impact Test

Product Dimension Drawing

Installation Precautions

1. The output ports of this series-type lightning protector are connected to the protected equipment.
2、Positive and negative lines should not be connected to the reverse or wrong, remember not to work with electricity.
3, lightning protector installed in the front of the protected equipment the closer the better.
4. The equipment needs to be inspected regularly, and the product must be replaced immediately after deterioration.