Tel. +86-755-82591856     E-mail. info@omrdon.com

Shenzhen OMRDON TECHNOLOGY

---- specializes in lightning safety and protection.

OMS-TNC-JK/3.0 天馈防雷器,TNC天馈避雷器,GPS基站天线避雷器 - 欧姆雷盾omrdon Technology

Coaxial RF Surge Protector/

OMS-TNC-JK/3.0 Antenna lightning protector, TNC antenna lightning arrester, GPS base station antenna lightning arrester

model number

OMS-TNC-JK/3.0
OMS-TNC-KK/3.0

Nominal discharge current (In)

10 KA (8/20μs)

Maximum discharge current (Imax)

20 KA (8/20μs)

DC breakdown voltage (100V/s)

90/230/350/600 Volts

Maximum pulse voltage (1KV/μs)

650/700/750/800 Volts

characteristic impedance

50Ω

VSWR

≤1.2

insertion loss

≤0.2 dB

frequency range

DC-3.0 GHz

  • 产品详情
  • Inquiry

OMS-TNC-JK/3.0.OMS-TNC-KK/3.0 Antenna lightning arrester, TNC antenna lightning arrester, GPS base station antenna lightning arrester

Product Description:

     OMRDON (OMRDON) TNC type antenna feeder lightning protector (SPD, surge protector) is suitable for all kinds of RF transceiver system, wireless network signal transmission, satellite TV receiving equipment, monitoring signal wireless transmission receiving equipment lightning protection. Widely used in communication stations, radar stations, SmarTone base stations, mobile communication base stations, GPS base stations, CDMA base stations, PHS (PAS) base stations, satellite communications, microwave stations and so on. It can prevent damage to antenna and transceiver equipment caused by overvoltage of feeder-induced lightning strikes, and is installed in the lightning protection sub-district LPZ0A-1 and subsequent sub-districts.

     The product is encapsulated in a shielded case with a built-in high quality high-speed overvoltage protection device, which provides efficient protection and defense against lightning high-voltage pulses induced on the antenna feeder line.

Functional Features::

  • Lightning impulse current up to 20KA
  • Maximum output power 400W
  • Frequency range DC-3.0GHz
  • DC Pass
  • F-type connector (female/male)
  • Very low VSWR <1.2
  • Characteristic impedance 50Ω
  • International Certification RoHS, CE, FCC

typical application::

  • GPS base station
  • WiFi
  • PHS (PAS) base station
  •  satellite communications
  • radar base station
  • microwave station

Technical Parameters

model numberOMS-TNC-JK/3.0
OMS-TNC-KK/3.0
Nominal discharge current (In)10 KA (8/20μs)
Maximum discharge current (Imax)20 KA (8/20μs)
Reaction time (Ta)≤100 ns
Maximum transmission power Pt400 Watts
DC breakdown voltage (100V/s)90/230/350/600 Volts
Maximum pulse voltage (1KV/μs)650/700/750/800 Volts
characteristic impedance50Ω
VSWR≤1.2
insertion loss≤0.2 dB
frequency rangeDC-3.0 GHz
Insulation impedance≥5000MΩ
interface methodTNC@JK, KK
Housing MaterialNickel Plated Brass/Ternary Alloy
Ground resistance and wire diameter≤4Ω /≥2.5mm2
sizes57.5*Φ25mm(JK), 51.5*Φ25mm(KK)
Operating Temperature Range-40 ~ +85℃,altitude ≤4km
Relative air humidity30%~90%
Protection class (IP)IP67
Compliance CertificationCE, RoHs,FCC,IP67,ISO9001-2015
Implementation standardsgb18802.21/lec61643-21/iec60169-4/iec60068-2-52
item number800411

Typical Performance Test Data

Simulated lightning impact test and typical performance test

Product Dimension Drawing


Installation Notes:

1, in order to reliably prevent lightning strikes, can be in the antenna output and the input of the protected equipment are connected in series with an antenna feed lightning arrester the antenna feed lightning arrester is not divided into input and output, the interface can be matched.

2, the lightning protector on the lug welding as short as possible grounding wire (wire area of not less than 4mm) 2), the other end is reliably connected to the lightning protection system grounding bus, and the grounding resistance is not more than 4Ω.

3, the product has a waterproof function, but in the outdoor use of the antenna feeder should also pay attention to rain, do not let the rain soak into its internal corrosion damage.

4, this product does not require special maintenance. When the system works faulty, you can remove the lightning protector and then check, if the system returns to normal after restoring to the state before use, it means that the lightning protector has been damaged and must be replaced immediately.

    personstradedistributor

    Prev:

    下一篇:

    在线留言

    这个站点使用 Akismet 来减少垃圾评论。了解你的评论数据如何被处理

    Leave a message