Tel. +86-755-82591856     E-mail. info@omrdon.com

Shenzhen OMRDON TECHNOLOGY

---- specializes in lightning safety and protection.

OMS-CS24-2S-UT2测控系统信号电涌保护器,7mm超薄外壳,20KA,2线制回路系统,B2,C2,D1,免拧螺丝,直插式接线 - 欧姆雷盾omrdon Technology

Signal line lightning protection/

OMS-CS24-2S-UT2 Signal Surge Protector for Measurement and Control Systems, 7mm Slim Housing, 20KA, 2-Wire Loop System, B2, C2, D1, Screwless, Plug-In Wiring

model number

OMS-CS24/2S-UT2

test level

B2, C2, D1

Nominal operating voltage (Un)

24 V

Maximum Continuous Operating Voltage (UC)

33 V

B2 withstand impulse voltage (Uoc)

6KV (10/700μs)

C2 Nominal inrush current (In)

10KA (8/20μs)

C2 Maximum inrush current (Imax)

20KA (8/20μs)

D1 lightning impulse current (Iimp)

2.5KA (10/350μs)

interface method

Direct plug-in cage terminals

Housing Material

PA66 UL94-V0

Through grounding

DIN rail/terminal

sizes

64*7*93mm

  • 产品详情
  • Inquiry

6V, 12V, 24V, 48V Measurement and control signal system with 7mm ultra-thin signal lightning protector, 20KA, 2-wire (1 channel), direct plug-in wiring, no screws, convenient and time-saving labor.

Product Description:

OMRDON Slim Series Signal Surge Protectors (SPD, Surge Protectors) are designed with 7mm ultra-thin housing, which does not take up installation space, and adopts direct plug-in cage terminals, which is very convenient for wiring without screwing and saves installation time.

This series of products is mainly applicable to the measurement and control system RS485/422 CAN bus, 4-20mA and other analog signals, switching signals line lightning electromagnetic pulse (LEMP) surge protection, installed in the lightning protection zone 1-2 and 2-3 zone.

Functional Features::

  • Protects 1 circuit (single channel).
  • Maximum surge inrush current 20KA.
  • Built-in overcurrent and overheating fuse/release protection.
  • 7mm ultra-thin case that doesn't take up much space.
  • Plugs directly into cage terminals without screwing.
  • Multiple operating voltage options: (6V/12V/24V/48V/110V).
  • Complies with CE, RoHS and FCC standards.

typical application::

  • RS485
  • 4-20mA
  • AI (analog signal)
  • DI (Digital Signal)
  • switching signal

Technical Parameters::

electronicparameters

model numberOMS-CS24/2S-UT2
test levelB2, C2, D1
Nominal operating voltage (Un)24 V
Maximum Continuous Operating Voltage (UC)33 V
B2 withstand impulse voltage (Uoc)6KV (10/700μs) @X-PE
C2 Nominal inrush current (In)10KA (8/20μs)
C2 Maximum inrush current (Imax)20KA (8/20μs)
D1 lightning impulse current (Iimp)2.5KA (10/350μs)
Voltage protection class (Up)X-X≤60V, X-PE≤650V
Response time (Ta)≤1 ns
Nominal Current (IL)1A
series resistance3.3 Ω
Typical Capacitance≤1pf
insertion loss≤0.2 dB
frequency range10 MHz

(old) cunningparameters

interface methodDirect plug-in cage terminals
Housing MaterialPA66 UL94-V0
Through groundingDIN rail/terminal
sizes64*7*93mm
weights60g [0.15 Ibs]

Environmental norms

Temperature operating range-40 ~ +85℃,Altitude≤4km
Environmental humidity30%~90%
Enclosure protection class (IP)IP20

Other information

Compliance CertificationCE, RoHs, FCC, ISO9001-2015
Test Standardsgb/t18802.21 / iec61643-21
Order No.80034341

Series Model Information

Simulated Lightning Impact Test

Product Dimension Drawing

Installation Precautions

1, this protector can be installed in zones 1-2 and 2-3, directly installed in series in the front of the protected equipment (or system), the closer the installation is to the protected equipment (or system), the better;

 2、“In ”connecting the lead end, “OUT ”connecting the end of the protected equipment (or system), “1” and “3“ is a signal channel, ”2“ and ”4" is a signal channel. "1" and "3" is a signal channel, "2" and "4" is a signal channel. When installing the two ends of the line must be laid separately, not bundled together to prevent secondary induction phenomenon;

 3. The lightning protector grounding is connected with the shortest possible wire. The protector is grounded by means of terminal grounding or through the DIN rail, and the grounding wire must be connected to the lightning protection ground (or chassis/cabinet enclosure). The shielded wire of the signal can be connected directly to the grounding terminal;

 4, the lightning protector is installed under conditions that do not exceed the requirements is not required long-term maintenance, only routine maintenance of the system; such as in the process of use, signal transmission problems, change the surge protector after the signal transmission back to normal, indicating that the surge protector has been damaged, need to be repaired or replaced.

 

    personstradedistributor

    下一篇:

    在线留言

    这个站点使用 Akismet 来减少垃圾评论。了解你的评论数据如何被处理